![Huawei NetCol8000-A Series Скачать руководство пользователя страница 71](http://html.mh-extra.com/html/huawei/netcol8000-a-series/netcol8000-a-series_user-manual_166611071.webp)
NO TICE
● Connections of all power cables, control cables, and ground cables must comply
with the local electrical code, and the cable specifications should comply with
the local cabling specifications.
● For details about the currents in full load, see the NetCol8000-A nameplate.
● The required main power is 380–415 V AC, 3 N, 50 Hz.
● Only trained and qualified personnel are allowed to connect cables.
● Before connecting cables, use a voltmeter to measure the input voltage and
ensure that the power supply is off.
● All the NetCol8000-As should be safely grounded.
● Keep cables away from the compressors, fans, and copper pipes (otherwise,
take protective measures), and cables should be properly connected.
3.6.2 Electrical Ports of an Indoor Unit
Electrical Ports
Open the front doors, you can see the electrical ports inside the electrical control
box. The external ports include a power port, network port of the main control
board, and port for the control cable routed from the control cable terminal.
Figure 3-41 NetCol8000-A050 external ports of the electrical control box
(1) Main control board
(2) Voltage jumper port
(3) External cable terminal
(4) General circuit breaker
(power port)
(5) Main PE bar
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
3 Installation Guide
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
62