Table 2-7 Performance parameters of the NetCol8000-A series product
Parameter
NetCol8000-A100D
NetCol8000-A050D
Power
380 V to 415 V AC, 3Ph, 50 Hz (Single power supply)
Voltage tolerance
a
Rated voltage ± 10%
The maximum three-phase voltage imbalance cannot
exceed 4%.
b
Frequency tolerance
Rated frequency ± 3 Hz
Cooling capacity (kW)
100
50
Sensible cooling
capacity (kW)
93.5
46.8
Number of fans (PCS)
2
1
Airflow volume of the
indoor unit (m
3
/h)
28000
14000
Maximum operating
current of the indoor
unit (A)
76
38
Refrigerant
R410A
Electrical heater
power (kW)
12
6
Humidifier capacity
(kg/h)
10
7
Level of filters
G4
Number of filters
(PCS)
4
2
Dimensions (H x W x
D) (mm)
1980 x 2280 x 890
1980 x 1140 x 890
Gross/Net weight (kg) 967/830
520/415
a: Recommended to add the voltage regulator in the front end if the power
exceeds this range. Otherwise, smart cooling product will generate frequency
alarms and cannot run.
b: Three-phase voltage imbalance can cause large current at some winding of
the motor, resulting in overheating, and may damage the motor. Formula for
calculating the three-phase voltage imbalance: Voltage imbalanc ε = (|V
avg
-
V
AB
|, |V
avg
- V
BC
|, |V
avg
- V
CA
|)/V
avg
x 100%, V
avg
= average voltage of phases A,
B, and C; V
AB
= voltage between phase A and phase B; V
BC
= voltage between
phase B and phase C; V
CA
= voltage between phase C and phase A.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
2 Product Description
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
22