Step 2 Set the time and date and tap Next, as shown by (2) in
Step 3 Set system parameters and tap Finish, as shown by (3) in
Step 4 The system displays a dialog box for confirming the rated voltage. Tap Yes after
confirmation, as shown by (4) in
.
----End
5.4 Initial Configuration
NO TICE
● When configuring the temperature and humidity parameters, do not place the
cursor between the decimal point and the following digit of the value.
Otherwise, the decimal point cannot be deleted, and the parameter value fails
to be configured.
● To ensure the security of user information, you need to import a certificate and
key before using the controller, and periodically update the certificate and key.
For details about how to import a certificate and key, see
.
5.4.1 User Right Authentication
To enhance security, before a user attempts to perform setting and maintenance
operations, the user needs to enter the user name and password for right
authentication.
shows the setting login screen for an example.
Figure 5-4 Screen for logging in to the settings screen
●
Users include Admin, Engineer, Operator, and Guest. The Admin users have
the highest permission, followed by the Engineer, Operator, and Guest users.
The initial passwords for the Admin, Engineer, and Operator users are all
000001. The Guest user does not have a initial password.
●
To prevent misoperation, log in as Operator users first before modifying
parameters. Obtain permission from Huawei before modifying any parameter
that you are not allowed to modify, otherwise, Huawei will not be liable for
any consequences of the modification.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual