![Huawei NetCol8000-A Series Скачать руководство пользователя страница 188](http://html.mh-extra.com/html/huawei/netcol8000-a-series/netcol8000-a-series_user-manual_166611188.webp)
Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a117 Group
units
numbe
r not
match
Major N/A
1. Slave unit's
Teamwork Settings
are incorrect.
2. Master unit's
Teamwork Settings
are incorrect.
3. Slave unit dropped.
1. Modify slave
unit's
Teamwork
Settings, join
the Teamwork
Group.
2. Modify the
master unit's
Total number
of
unitsaccordin
g the actual
number.
3. Check slave
unit's
Teamwork
Wire
connection
and Running
Condition.
7.3 Troubleshooting
NO TICE
● Certain circuits in the NetCol8000-A have lethal voltage. Only professional
technicians are allowed to perform maintenance. Exercise caution during live-
line troubleshooting.
● If jumpers are used for troubleshooting, remove them after troubleshooting.
Connected jumpers may affect control functions and damage equipment.
Table 7-9 NetCol8000-A troubleshooting
Symptom
Possible Cause
Reference Solution
The NetCol8000-A
generates abnormal
voice.
Compressor, fans, or pipes
are loose.
Check the fixing structure
and ensure that all
components are securely
installed.
A compressor does
not work.
The high pressure switch
reacts.
Check the high pressure
switch status.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
179