Figure 7-11 Removing screws securing the fan to the bottom plate
Step 15 Install a new indoor fan in an inverse order.
Step 16 Power on the unit and tap Maint > Diagnostic Mode > Enter. Set the indoor unit
to lower speed, make sure they work properly, and then exit the Diagnostic
Mode.
Step 17 Tap Maint > Performance Maint to clear the indoor fan total runtime.
----End
7.4.3 Replacing a Compressor
Prerequisites
Required tools: two adjustable wrenches, a torque wrench, a welding torque, a
nitrogen cylinder (to be prepared onsite), LOCTITE 554 glue (optional), a new
compressor, and a new dryer filter.
Context
D ANGER
When replacing a compressor, avoid skin contact with the refrigerant or lubricant
to prevent frostbite or burns.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
188