Parameter
Specifications
Operation temperature of
cooling system
18°C to 32°C.
The temperature range of
the outdoor unit
Outdoor unit (NetCol500-A072): –20°C to
+ 45°C. (If low-temperature component is used,
the lowest temperature is -40°C.)
Outdoor unit (NetCol500-A088): –20°C to
+ 55°C.
Protection level
Indoor unit: IP20.
Outdoor unit: IPX5.
Storage temperature
–40°C to +70°C.
Storage humidity
5% RH to 95% RH (non-condensing).
Altitude
0 m to 1000 m. The refrigerating capacity is
derated when the altitude is above 1000 m. For
Water requirements to the
humidifier
The sum of calcium and magnesium cannot
exceed 600 mg/L.
Table 2-6 Derating coefficients
Altitude
0
1000
1500
2000
2500
3000
3500
4000
Density
coefficien
t
1
0.887
0.835
0.785
0.737
0.692
0.649
0.608
Air
volume
coefficien
t
1
0.887
0.835
0.785
0.737
0.692
0.649
0.608
Cooling
capacity
coefficien
t
1
0.940
0.909
0.878
0.846
0.815
0.784
0.753
2.4 Performance Parameters
The following table lists the performance parameters of the NetCol8000-A series
product.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
2 Product Description
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
21