Figure 3-8 Layout for the scenario where the outdoor unit is placed higher than
the indoor unit (unit: m)
(1) Tilted discharge pipeline
NO TE
● The gradients of the discharge pipeline are at least 1: 200.
● The graphic in dotted box shows the installation layout for NetCol8000-A050.
●
If the indoor unit is placed higher than the outdoor unit.
Figure 3-9 Layout for the scenario where the indoor unit is placed higher than the
outdoor unit (unit: m)
(1) Tilted discharge pipeline
(2) Tilted liquid pipeline
NO TE
● The gradients of the liquid pipeline and the discharge pipeline are at least 1: 200.
● The graphic in dotted box shows the installation layout for NetCol8000-A050.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
3 Installation Guide