Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a002 Return
-air HT
Critic
al
The
temperatu
re and
humidity
collection
board
measures
the return
air
temperatu
re 90 s
after a
fan start
signal is
sent. This
alarm is
generated
if the
return air
temperatu
re reading
is valid
and
greater
than the
high
temperatu
re alarm
threshold
when the
alarm
detection
delay
expires..
1. The load is high or
the refrigeration
capacity is
insufficient.
2. The return air
temp is higher
than the return-air
HT alarm thres
during startup.
3. The ambient temp
is high.
4. The return-air HT
alarm thres is
inappropriate.
5. The temp displayed
is different from
the actual temp.
1. Add more
smart cooling
product units.
2. Check other
causes if the
alarm persists
after startup.
3. Check the
ambient
temp.
4. Adjust the
return-air HT
alarm thres.
5. Calibrate or
replace the
abnormal
temp sensors.
For details
about how to
calibrate the
sensor, see
.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
156