![Huawei NetCol8000-A Series Скачать руководство пользователя страница 169](http://html.mh-extra.com/html/huawei/netcol8000-a-series/netcol8000-a-series_user-manual_166611169.webp)
Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a009 Comp
HP
lock
Critic
al
A
compresso
r has
triggered
six high
pressure
alarms
within
one
consecutiv
e hour, or
a
compresso
r high
pressure
alarm is
not
cleared
within 10
minutes.
The a008 comp HP
alarm is generated
frequently.
Reference to the
solutions for the
a008 comp HP
alarm.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
7 System Operation and Maintenance
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
160