Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a093 High
humidi
ty
Warni
ng
The return
air
humidity
reading is
valid and
greater
than the
high
humidity
alarm
threshold
when the
alarm
detection
delay
expires
90s after
a fan
startup
signal is
sent.
1. The load is low.
2. The T/H sensors
are located in
inappropriate
position.
3. The ambient
humidity is high.
4. The high humidity
alarm thres is
inappropriate.
5. The humidity
displayed is
different from the
actual humidity.
1. Please consult
Huawei
technical
support.
2. Adjust the
position of
the T/H
sensors.
3. Check the
ambient
humidity.
4. Adjust the
high humidity
alarm thres.
5. Calibrate or
replace the
abnormal T/H
sensors.
a094 Low
humidi
ty
Warni
ng
The return
air
humidity
reading is
valid and
lower
than the
low
humidity
alarm
threshold
when the
alarm
detection
delay
expires
90s after
a fan
startup
signal is
sent.
1. The T/H sensors
are located in
inappropriate
position.
2. The ambient
humidity is low.
3. The low humidity
alarm thres is
inappropriate.
4. The humidity
displayed is
different from the
actual humidity.
1. Adjust the
position of
the T/H
sensors.
2. Check the
ambient
humidity.
3. Adjust the
low humidity
alarm thres.
4. Calibrate or
replace the
abnormal T/H
sensors.