If the information shown in
is displayed on the controller LCD,
the smart cooling product cannot run properly. Perform
to end.
Figure 5-57 Message 2
NO TE
In the
the ACC V100R001C20SPC300 version is used as an example to describe
the prompt messages on the screen. During actual operations, the version in use prevails.
Procedure
Step 1 Check whether strong electromagnetic interference exists around the E-label
identification board.
●
If yes, contact Huawei technical support.
●
If no, continue with
Step 2 Disconnect the main power supply of the smart cooling product.
Step 3 Check whether the E-label identification board is properly connected.
●
If no, reconnect the board properly and continue with
●
If yes, continue with
Step 4 Check whether cables are properly connected.
●
If yes, contact Huawei technical support to replace the E-label identification
board.
●
If no, reconnect or replace cables and perform
.
Step 5 Reconnect the main power supply of the smart cooling product.
Step 6 If the fault persists, contact Huawei technical support.
----End
5.19 How to Import a Certificate and Key
Prerequisites
You have obtained CA certificate file, local certificate file, and key file into a
USB disk.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
139