Alar
m ID
Alarm
Name
Alar
m
Sever
ity
Occurren
ce
Condition
s
Possible Causes
Solutions
a046 Comp
freeze
point
protect
ion
Critic
al
The
antifreeze
low
pressure
protection
switch is
triggered,
and the
alarm
detection
delay
expires.
1. The refrigerant
leaks.
2. The solenoid valve
is faulty.
3. The cables to the
low press sensor
are loose or
damaged.
4. The low press
sensor is faulty.
5. The filter dryer is
blocked.
6. The expansion
valve is blocked.
1. Check for any
leakages. Fill
refrigerant
after
maintenance
or
replacement.
2. Maintain or
replace the
solenoid coil
or the
solenoid
valve.
3. Check the
cables to the
low press
sensor.
4. Maintain or
replace the
low press
sensor.
5. Maintain or
replace the
filter dryer.
6. Maintain or
replace the
expansion
valve.
a083 Surge
protect
ion
board
fault
Critic
al
N/A
1. The SPD is faulty.
2. The cables to the
SPD are loose or
damaged.
3. The port of the
control board is
faulty.
1. Maintain or
replace the
SPD.
2. Check the
cables to the
SPD.
3. Maintain or
replace the
control board.