3.1.6 Installation Requirements
Requirements for Installing an Indoor Unit
1. The shelter should have good heat insulation, and the walls and floor should
be protected against moisture.
2. During the NetCol8000-A operation, all doors and windows of the shelter or
equipment room should be closed to reduce the additional load.
3. To ensure good ventilation, do not place the indoor unit in the corner of a
room or the end of a long-and-narrow room.
4. Ensure that a minimum of 800 mm maintenance space is reserved in front of
the indoor unit.
5. When the pipes are routed through the side panel, the distance between two
indoor units or between an indoor unit and a wall is at least 600 mm.
6. When the pipes are routed through the bottom plate, two indoor units can be
installed closely in parallel and can be maintained from the front.
Figure 3-10 Requirements for routing pipes (unit: mm)
(1) Indoor unit
Requirements for the Raised Floor Support
The indoor fan should be lowered under the raised floor, if the NetCol8000-A100D
and NetCol8000-A50D adopt downward supply mode. Therefore, the shelter
should be equipped with a raised floor, and the support for the raised floor should
be at least 400 mm in height.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
3 Installation Guide
Issue 12 (2020-10-28)