Figure 3-43 Routing the cables for the NetCol8000-A100
(1) General cables connection
(2) Control ports cables connection
(3) Network group control cables connection
(4) PE cables connection
3.6.3 Connecting the Power Cable to the Indoor Unit
NO TICE
● To ensure that the smart cooling product is effectively grounded, route a
ground cable from the PE ground bar of the indoor unit to the ground bar of
the shelter.
● For the details about the outdoor unit, see the Outdoor Unit User Manual.
L1, L2, L3, N, and PE connect to corresponding ports on the external power supply.
The following figure shows the zoomed-in view of the power port.
Cables are selected based on the maximum operating current of the indoor unit,
and are installed with cord end terminals at both ends. The maximum operating
currents of the NetCol8000-A100 and NetCol8000-A050 are 84 A and 42 A
respectively. The specifications of the general power cables for the two models are
5x25 mm
2
and 5x16 mm
2
respectively.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
3 Installation Guide