| Modes/ program/functions
F1 (min)
the minimum allowed value for the relative internal humidity. the control is
switched off when the internal humidity has fallen below this value. this can
prevent unwanted dehydration.
Setting range:
0.1% RH ... 100% RH
Factory setting:
20% RH
REL T1 delay
By entering a value to ReL t1 delay, the switch-on delay for the relay t1 is
defined. this setting prevents frequent switching of the relay t1, with rapidly
changing dew-point temperatures tP1 or tP2, relatively small dew-point
differences, or with rapidly changing temperatures.
Setting range:
0 to 60 sec
Factory setting:
0 sec
PARAMETER OVERVIEw OF RELAy T1
Abbreviations:
T1
measured temperature at internal sensor (sensor 1)
TP1
calculated dew point temperature at internal sensor (sensor 2)
TP2
calculated dew point temperature at outdoor sensor (sensor 2)
dTP
calculated difference tP1 - tP2
TP_diff_On
setpoint for the difference tP1 - tP2 (switch on)
TP_diff_Off
setpoint for the difference tP1 - tP2 (switch off)
T1 (min)
setpoint for the minimum allowed internal temperature
T1 (max)
setpoint for the maximum allowed internal temperature
F1 (min)
setpoint for the minimum allowed relative humidity (interior)
NOTE:
If a sensor is faulty or not connected, the relays will be turned off.