62
|
the parameters have the following meaning:
Interval ON
Defines the value Interval oN determines how long the relay t1 or the
connected fan is switched on for a limited time.
Setting range:
5..20 min
Factory setting:
10 min
Interval OFF
Defines the value Interval oFF determines how long the relay t1 or the
connected fan is switched on for a limited time.
Setting range:
20...120 min
Factory setting:
30 min
T1 (min)
the value for the indoor temperature defines the minimum acceptable tempera-
ture. the control is switched off when the internal temperature has reached this
value. An undesirable cooling of the room is prevented.
Setting range:
-40 °C … +120 °C
Factory setting:
10 °C
T1 (max)
Defines the value for the indoor temperature defines the maximum acceptable
temperature. the control is switched off when the internal temperature has
exceeded this value. An heating of the room is prevented. this can e.g. be
interesting for a vegetable storage or a wine cellar.
Setting range:
-40 °C … +120 °C
Factory setting:
30 °C
F1 (min)
Defines the minimum allowed value for the relative internal humidity. the
control is switched off when the internal humidity has fallen below this value.
this can prevent unwanted dehydration.
Setting range:
0,0 % RH … 100 % RH
Factory setting:
20 % RH
Modes/ programs/functions