76
|
T1_
AUS
T1_
T1_
T1_EIN
25 °C
22 °C
Hysterese 3 °C
HEATINg
TEMPERATURE
TIME
Switch-on point
T1 OFF
T1 ON
Switch-off point
hysteresis 3°C
T1(2)
25°C
22°C
Behavior of the relay T1 or T2
Abbreviations:
T1
measured temperature at the indoor sensor
T1 EIN
setpoint of the switch-on temperature
T1 AUS
setpoint for the switch-off temperature
Relay t1 is switched on when
T1 ≤ T1 ON
Relay t1 is switched off when
T1 ≥ T1 OFF
NOTE:
All relays are switched off if the indoor sensor or outdoor sensor is
faulty or not connected.
COOLINg FUNCTION IN TF SwITCH MOdE
Modes/programs/functions
Anleitung_PLS1000_DE_EN.indd 76
13.12.19 12:40