63
Professional humidity switch PLS1000
REL T1 delay
Defines the switch-on delay for the relay t1. this setting prevents frequent
switching on or off of relay t1, with rapidly changing dew point temperature
or humidity.
Setting range:
0 … 60 s
Factory setting:
0 s
BEHAVIOR OF RELAy T1
Abbreviations:
T1
measured temperature at the internal sensor (sensor 1)
TP1
calculated dew point temperature at the internal sensor (sensor 2)
TP2
calculated dew point temperature at the outdoor sensor (sensor 2)
dTP
calculated difference tP1 - tP2
Interval ON
setpoint for the time interval oN
Interval OFF
setpoint for the time interval oFF
T1 (min)
setpoint for the minimum permitted internal temperature
T1 (max)
setpoint for the maximum permitted internal temperature
F1 (min)
setpoint for the minimum permissible relative humidity (interior)
the relay is
switched on
for the interval „
Interval ON
“ if:
t1 ≥ t1 (min) and t1 ≤ t1 (max) and F1 ≥ F1 (min) and dtP ≥ 1 °C.
the relay is
switched off
when:
t1 <t1 (min.) or t1> t1 (max) or F1 <F1 (min) or dtP <1 °C or the time interval
„Interval OFF“
is running.
NOTE:
If a sensor is faulty or not connected, the relays will be turned off.
NOTE:
If you want to operate the „Interval Ventilation“ mode independent
of the current indoor temperature, select for t1 (min.) -40 °C and for t1 (max.)
+120 °C.