Professional humidity switch PLs1000
the „cooling“ function is set if the set switch-on temperature is greater than the
switch-off temperature. the fans are switched the relay t1 or t2.
Example:
you want to control a cooling unit. the desired top temperature is
e.g. 12 °C. the cooling unit / unit should switch on when the temperature
rises above 12 °C (t 1 eIN = 12 °C) and z. B. turn off at 10 °C again. In this
case the hysteresis is 2 °C.
T1_AUS
T1_EIN
12 °C
Hysterese 2 °C
10 °C
COOLINg
TEMPERATURE
TIME
Switch-on point
T1 ON
T1 OFF
Switch-off point
T1(2)
hysteresis 2°C
Behavior of the relay T1 or T2
Abbreviations:
T1
measured temperature at the indoor sensor
T1 EIN
setpoint of the switch-on temperature
T1 AUS
setpoint for the switch-off temperature
Relay t1 is switched on when
T1 ≥ T1 ON
Relay t1 is switched off when
T1 ≤ T1 OFF
NOTE:
All relays are switched off if the indoor sensor or outdoor sensor is
faulty or not connected.
„HUMIdIFy“ FUNCTION IN TF-SwITCHINg MOdE
the „Humidify“ function is set when the set switch-on humidity value is less than