Professional humidity switch PLS1000
REL F1 timer
the switch-on delay ReL F1 delay entered in the process: setting can be viewed
in this menu item and shows the remaining time, from reaching the set setpoint
values, until the switching operation.
REL F2 timer
the switch-on delay ReL F2 delay entered in the process: setting can be viewed
in this menu item and shows the remaining time from reaching the set setpoint
values until switching.
Settings (read only) ...
In this menu item, the settings made can be checked without leaving the control
process „tF switch“. to do this, select the menu item
„Settings (read only) ...“
with the
Ok
button. Use the
,
keys to call up and view the settings made.
You can only make changes in the settings process. With the help of the
ESC
key, you leave this menu item and return to the control process.
„HEATINg“ FUNCTION IN TF SwITCH MOdE
The „Heating“ function is activated if the set switch-on temperature is lower than
the switch-off temperature. The fans are switched the relay T1 or T2.
Example:
you want to control the room temperature by using a fan heater. The
desired temperature should e.g. in the range between 22 °C and 25 °C. The
fan heater should—when the temperature falls below 22 °C—turn on (T1 ON
= 22 °C) and turn off again when reaching 25 °C. In this case the hysteresis
is 3 °C. The relay is switched on when the measured temperature is lower than
or equal to T ON. The relay is switched off when the measured temperature is
greater than or equal to T OFF.