79
Professional humidity switch PLs1000
than the off-set humidity value. the control is carried out by the relay F1 or F2.
F1_AUS
F1_EIN
HUMIdITy
TIME
Switch-on point
F1 ON
F1 OFF
Switch-off point
dEHUMIdIFy
F1(2)
hysteresis
Behavior of relay F1 or F2
Abbreviations:
F1
measured relative humidity at the indoor sensor
F1 EIN
setpoint for the switch-on humidity
F1 AUS
setpoint for the switch-off humidity
Relay F1 turns on when
F1 ≥ F1 ON
Relay t1 is switched off when
F1 ≤ F1 AUS
NOTE:
All relays are switched off if the indoor sensor or outdoor sensor is
faulty or not connected.
7.6 MANUAL CONTROL
In this mode, all potential-free relays T1, F1, T2 and F2 can be manually
switched on and off.