68
|
Relay is switched on when:
T1 > T2
and
T1 ≥ T1 ON
Relais wird ausgeschaltet, wenn:
T1 ≤ T2
or
T1 ≤ (T1 ON - T1 hysteresis)
NOTE:
If a sensor is faulty or not connected, the relays will be turned off.
PROgRAM: CONTROL
the following menu items can be displayed:
PROgRAM: dT-Belüftung (dT ventilation)
Temperature T1
Temperature T2
dT=T1-T2
REL T1 timer
Einstellungen (nur lesend)… /
Settings (read only) ...
the parameters have the following meaning:
Temperature T1
Currently measured temperature at the indoor sensor (degrees Celsius)
Temperature T2
Currently measured temperature at outdoor sensor (degrees Celsius)
dT=T1-T2
determined temperature difference between indoor sensor and outdoor sensor
(degrees Celsius)
REL T1 Timer
the switch-on delay ReL t1 time entered in the process can be viewed in this menu
item and shows the remaining time, from reaching the set setpoints, until switching.
Settings (read only) ...
the settings can be checked without leaving the process „Interval Ventilation“.
to do this, select the bottom menu item
„Settings (read only) ...“
with the
Ok
button. With the help of the keys
,
you can call up and view the settings
made. Changes can only be made during the set-up menu. to return to the set-
up menu, press the esC key.