Professional humidity switch PLs1000
PROgRAM: SET
the following menu items are displayed and can be changed:
T1 EIN /
T1
ON
T1 Hysterese /
T1 hysteresis
REL T1 delay
the parameters have the following meaning:
T1 ON
the switch-on temperature defi nes the switching temperature of the relay t1.
Setting range:
-40°C bis +120°C
Factory settings:
23°C
T1 Hysterese
the hysteresis prevents frequent switching on or off of the relay t1 if the measured
temperature at the inside sensor t1 is equal or frequently in the same range of
the set target temperature t1 eIN (on).
Setting range:
1 bis 5°C
Factory settings:
1°C
REL T1 delay
the of ReL t1 delay shows the set the switch-on delay for the relay t1. this
setting prevents frequent switching on or off of the relay t1 by slightly fl uctuating
temperatures or if setpoints t1 eIN (on) or t1 hysteresis have almost the same
values.
Setting range:
0 bis 60 sek
Factory settings:
0 sek
Behavior of relay T1
Abbreviations:
T1
measured temperature at the indoor sensor
T2
measured temperature at the outdoor sensor
T1 EIN /
T1 ON
setpoint for the switch-on temperature
T1 Hysterese
setpoint for the hysteresis