Professional humidity switch PLS1000
PROFESSIONAL HUMIdITy
SwITCH
PLS1000
Art.- No. 1114630
SPECIFICATIONS
– Operating voltage: 230 V / AC (50 Hz) ± 10 %
– Power consumption (relative idle state): approx. 1 W
– Switching voltage per relay (AC): max. 230 V / AC max. 12 A
– Switching voltage per relay (DC): max. 24 V / DC max. 10 A
– Max. Switching capacity (total): approx. 2700 VA
– Resolution: 0.1 °C, 0.1% RH, 0.1 g / m³, 1 s
– Settings: 0.1 °C, 0.1% RH, 1 s increments
– Temperature range: -25 °C to +70 °C
– Accuracy: -25 °C to + 5 °C (max +/- 0,7 °C)
+5 °C to +60 °C (+/- 0,3 °C)
+60 °C to +70 °C (max +/- 0.9 °C)
– Humidity measurement range: 0% RH to 100% RH
– Accuracy: 0% RH to 20% RH (max +/-4.5% RH)
20% RH to 80% RH (+/-3% RH)
80% RH to 100% RH (max +/-4.5% RH)
– Sensors: 2x TH-1 humidity sensor (included)
– Sensor cable: 10 m (extendable up to 50 m)
– Operating temperature: +0 °C to 50 °C
– Protection class: IP20
1. dESIgNATEd USE
the professional humidity switch PLs 1000 can measure the current relative humi-
dity and the current temperature in two environments with the help of two humidity
sensors tH-1. the PLs 1000 uses these values to determine the absolute humidi-
ty and the respective dew points. Based on these values, 6 integrated functions
(modes), different humidity and temperature controls can be programmed. Fans
for incoming air and exhaust air can be controlled directly through 4 integrated
potential-free relays. typical applications are the measurement of humidity and
temperature, automatic ventilation, the drying or humidifying of rooms, manual
control of room fans and the setup of a 2-channel temperature and humidity switch.
NOTE:
the housing and cables of the sensors are not intended for measurements
below -25 °C or above 70 °C.