the parameters have the following meaning:
T1 EIN
the switch-on temperature controls at which temperature the relay t1 should
be switched on.
Setting range:
-40°C to +120°C
Factory setting:
23°C
T1 AUS
the switch-off temperature indicates at which temperature the relay t1 should
be switched off.
Setting range:
-40°C to +120°C
Factory setting:
22°C
REL T1 delay
the function ReL t1 delay sets the switch-on delay for the relay t1.
this setting prevents frequent switching of the relay t1, if the values t1 oN or
t1 oFF are almost identical at slightly fluctuating temperatures.
Setting range:
0 to 60 sec.
Factory setting:
0 sec.
T2 EIN
the switch-on temperature indicates from which temperature the relay t2 should
be switched on.
Setting range:
-40°C to +120°C
Factory setting:
23°C
T2 AUS
the switch-off temperature indicates at which temperature the relay t2 should
be switched off.
Setting range:
-40 °C to +120 °C
Factory setting:
22 °C
REL T2 delay
the function ReL t2 delay sets the switch-on delay for the relay t2.
this setting prevents frequent switching of the relay t2, if the values t2 IN and
t2 oFF are almost identical with slightly fluctuating temperatures.
Setting range:
0 to 60 sec.
Factory setting:
0 sec.