Professional humidity switch PLs1000
the parameters have the following meaning:
TP_diff_ON
By setting the dew point difference to oN, the deviation between the dew
point tP1 and tP2 defi nes the value at which relay t1 should switch on.
Setting range:
2 to 10 °C (see note)
Factory setting:
5 °C
NOTE:
At least 1 °C difference than the set value for tP_DIFF_oFF is required.
TP_diff_OFF
By setting the dew point difference to oFF, the deviation between the dew
point tP1 and tP2 defi nes the value at which the relay t1 should switch off.
Setting range:
1 to 9 °C (see note)
Factory setting:
1 °C
NOTE:
At least 1 °C difference than the set value for tP_DIFF_oN is required.
T1 (min)
the minimum allowed value for the internal temperature. Relay t1 or the
connected fan is switched off when the inside temperature falls below the
set t1 (min) value and the current outside temperature is lower than the current
inside temperature.
Setting range:
-40 °C to + 120 °C (see note)
Factory setting:
10 °C
NOTE:
At least 1 °C difference than the set value for t1 (max) is required.
T1 (max)
The maximum allowed value for the internal temperature. Relay t1 or the con-
nected fan is switched off when the internal temperature rises above the set
t1 (max) value and the current outdoor temperature is higher than the current
indoor temperature.
Setting range:
-40 °C to +120 °C (see note)
Factory setting:
30 °C
NOTE:
At least 1 °C difference than the set value t1 (min) is required.