Sensepoint XCD RFD Technical Manual
SPXCDHMRFEN Issue 4_08-2016
25
8.2 System Status
Display indications, current output and relay states for various operational conditions
are shown in the following table. For further details of error messages and trouble shooting
see section 12.3.
System Status
Status
Display
Current Output
Relay
Back
Light
A1
A2
Fault
Fault:
Circuit or sensor
error
F-XX
fault number
with fault icon
blinking
0-1.0 mA
Yellow,
flashing
System Fault
N/A
0-0.15mA
Note: In the event of processor failure the watchdog will automatically reset the system for
recovery.
Warning
W-XX
warning number
with fault icon
blinking
Dependent on
system status
Green
Steady
Normal
0.0
Gas
concentration
4-20 mA
Green
Steady
Alarm 1
Gas
concentration.
1
st
alarm icon
blinking
4-20 mA
Red,
flashing
Alarm 2
Gas
concentration.
2
nd
alarm icon
blinking
4-20 mA
Red,
flashing
Over-range
Full scale icon
and reading
blinking
22mA
Red,
flashing
Inhibit
Inhibit icon
dependent
on Menu
command. If
any relay is set
to inhibit relay,
then inhibit relay
will be activated.
2 or 4mA
depending on
configuration.
Green
Steady
Table 4: System status
Содержание Sensepoint XCD RFD
Страница 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Страница 59: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 59 17 6 Mounting Bracket Drawing ...
Страница 60: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 60 17 7 Sensepoint XCD RFD Sensor ...
Страница 64: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 64 China GB Ex English Version ...
Страница 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Страница 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Страница 67: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 67 18 3 European ATEX ATEX For Transmitter ...
Страница 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Страница 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Страница 79: ...www norrscope com ...