Sensepoint XCD RFD Technical Manual
SPXCDHMRFEN Issue 4_08-2016
74
22
Pentane
3*
23
Propane
5*
24
Propan-2-ol
4*
25
Styrene
2*
26
Tetra hydrafuran
4*
27
Toluene
3*
28
Triethylamine
3*
29
Xylene
2*
Table 14 . Star Rating of Gases
To cross calibrate the Sensepoint XCD flammable gas detector:
(1) Obtain the star rating for both the calibration test gas and the gas to be detected from
Table 14
(2) These values may then be used in Table 15 to obtain the required calibration span
setting when a 50% LEL test gas is applied to the detector.
*Rating of
*Rating of Gas to be Detected
Calibration
Gas
8* 7* 6* 5* 4* 3* 2* 1*
8*
50
62
76
95
- - - -
7*
40
50
61
76
- - - -
6*
33 41 50
62
78 - - -
5*
26 33 40 50 63 79 - -
4*
- 26 32 40 50 63 80 -
3*
- - 26 32 40 50 64 81
2*
- - - 25 31 39 50 64
1*
- - - - 25 31 39 50
Note: These settings must only be used with a calibration gas concentration of 50% LEL.
Table 15. Calibration span setting
(3) If a sensor is to be used to detect a gas other than that for which it was calibrated and
there is no intention to use an equivalent calibration gas to re-calibrate the sensor, then
the required correction factor may be obtained from Table 16.
The reading shown on the gas detector controller or transmitter display should be
multiplied by this number in order to obtain a more accurate gas concentration result.
Sensor calibrated to
Sensor used to detect
detect
8* 7* 6* 5* 4* 3* 2* 1*
8*
1.00 1.24 1.52 1.89 2.37 2.98 3.78 4.83
7*
0.81 1.00 1.23 1.53 1.92 2.40 3.05 3.90
6*
0.66 0.81 1.00 1.24 1.56 1.96 2.49 3.17
5*
0.53 0.66 0.80 1.00 1.25 1.58 2.00 2.55
4*
0.42 0.52 0.54 0.80 1.00 1.26 1.60 2.03
3*
0.34 0.42 0.51 0.64 0.80 1.00 1.27 1.62
2*
0.26 0.33 0.40 0.50 0.63 0.79 1.00 1.28
1*
0.21 0.26 0.32 0.39 0.49 0.62 0.78 1.00
Table 16. Correction factors
Содержание Sensepoint XCD RFD
Страница 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Страница 59: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 59 17 6 Mounting Bracket Drawing ...
Страница 60: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 60 17 7 Sensepoint XCD RFD Sensor ...
Страница 64: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 64 China GB Ex English Version ...
Страница 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Страница 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Страница 67: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 67 18 3 European ATEX ATEX For Transmitter ...
Страница 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Страница 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Страница 79: ...www norrscope com ...