Sensepoint XCD RFD Technical Manual
SPXCDHMRFEN Issue 4_08-2016
32
19.Promptly switch off the calibration span gas and remove the Sensepoint XCD
Gassing Cap from the sensor to allow the gas to disperse.
20.When the reading falls below 50% of the calibration gas level the display indicates a
countdown .
21. When the countdown is finished, the calibration procedure is complete.
22. The instrument returns to the ‘Set CAL’ menu. Activate the ‘
’ or ‘
’ switch to
select another menu or select ‘QuIT’ to return to normal monitoring mode.
Note: Remember to always replace the Weather Protection and other accessories.