6.4 Cabling
The use of industrial grade, suitably armoured field cable is recommended.
For example, screened 3 cores (plus screen 90% coverage), suitably mechanically
protected copper cable with a suitable M20 explosion-proof gland with 0.5 to 2.5 mm2 (20
to 13 AWG) conductors. Ensure the cable gland is installed correctly and fully tightened.
All unused cable entries must be sealed with a suitable certified sealing plug (one plug is
supplied).
Remote Mounting Cable Details
Type
Cable Spec
Max Length
RFD Remote
AWM2464 AWG20~AWG14 Shield
30meters
6.5 Cable and Earth/Ground regimes
Effective Earth/Ground bonding is important to ensure good EMC and RFI immunity.
The following diagrams show examples of how to earth/ground bond the cable at
enclosures. These bonding techniques provide good RFI/EMC performance. Earth/ground
loops must be avoided to prevent the risk of false signal variation.
Cable to Transmitter
Diagram 8: Controller Grounding
Diagram 9: System grounding
Cable outer sheath
Cable inner sheath
Clean / Instrument
Earth Screen
Controller
Power & Signal
Earth Screen
Controller
Transmitter
Note: The Sensepoint HT sensor requires an earth core if the remote junction box does
not have a suitable earth point.
Содержание Sensepoint XCD RFD
Страница 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Страница 59: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 59 17 6 Mounting Bracket Drawing ...
Страница 60: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 60 17 7 Sensepoint XCD RFD Sensor ...
Страница 64: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 64 China GB Ex English Version ...
Страница 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Страница 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Страница 67: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 67 18 3 European ATEX ATEX For Transmitter ...
Страница 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Страница 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Страница 79: ...www norrscope com ...