7 Default configuration
The Sensepoint XCD RFD transmitter is supplied with the following default configuration.
Function
Value/Setting
Meaning
Sensor Type
Automatic for Sensepoint XCD RFD
sensors. Must be set for Sensepoint
and 705 sensors.
XCD RFD recognizes the XCD RFD sensor cartridge
according to the gas type within its own sensor family
i.e. mV. For a Sensepoint and 705 sensor the user
must set the sensor type.
Signal output
≥0.0<1.0 mA
Fault (refer to table 9 section 12.3 for details)
2.0 mA or 4.0 mA
Inhibit (during configuration/user settings)
4.0 mA to 20.0 mA
Normal gas measurement
22.0 mA
Maximum over range
Alarm Relay 1*
Value is sensor dependant
Lower alarm level
De-energized
Energizes on alarm
Contact Normally Open (NO)
Closes on alarm
Alarm Relay 2*
Value is sensor dependant
Higher alarm level
De-energized
Energizes on alarm
Contact Normally Open (NO)
Closes on alarm
Fault Relay
<1mA
Detector Fault
Energized
De-energizes on alarm
Contact Normally Open (NO)
Closes on alarm
Inhibit
2.0 mA (default)
Signal output inhibited during menu use
If any relay is set to inhibit relay, then inhibit relay will
be activated.
Timeout
Disabled
No inhibit timeout. The detector waits for a button
press before returning to the previous state/setting
Timeout period can be set in ‘Configure Inhibit’ menu
in Configuration Mode.
Password
0000 (Disabled)
0000 (Password disabled). If changed then password
is activated.
Location
(Tag Number)
0000
Optional feature to identify the location or User’s “Tag”
number of the XCD
Temperature
o
C
Option to have
o
C or
o
F
Modbus
ID, baud rates and Parity bit
ID : 1
Baud rates : 19,200
Parity bit : EVEN
* Alarm relays automatically reset when reading falls within alarm thresholds. If relay configured to LATCH, then relays must be reset using
the Magnetic Wand.
Table 3: Default configuration
Gas Name
Default Range Lower Alarm Lower Alarm
Type
Higher Alarm Higher Alarm
Type
Sensepoint Flammable
100%LEL
20%LEL
Rising
40%LEL
Rising
Sensepoint HT Flammable
100%LEL
20%LEL
Rising
40%LEL
Rising
Sensepoint HT Flammable
20%LEL
10%LEL
Rising
15%LEL
Rising
705 Flammable
100%LEL
20%LEL
Rising
40%LEL
Rising
705 HT Flammable
100%LEL
20%LEL
Rising
40%LEL
Rising
XCD Flammable CB*
100%LEL
20%LEL
Rising
40%LEL
Rising
XCD Methane IR
100%LEL
20%LEL
Rising
40%LEL
Rising
XCD Propane IR*
100%LEL
20%LEL
Rising
40%LEL
Rising
Carbon Dioxide*
2.00%Vol
0.40%Vol
Rising
0.80%Vol
Rising
*Contact Honeywell Analytics for availability
For details of how to change the configuration of the Sensepoint XCD please refer
to section 13.
Содержание Sensepoint XCD RFD
Страница 1: ...Technical Handbook Sensepoint XCD RFD Remote Flammable Detector ...
Страница 59: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 59 17 6 Mounting Bracket Drawing ...
Страница 60: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 60 17 7 Sensepoint XCD RFD Sensor ...
Страница 64: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 64 China GB Ex English Version ...
Страница 65: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 65 China PA Certification ...
Страница 66: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 66 18 2 Korea KTL ...
Страница 67: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 67 18 3 European ATEX ATEX For Transmitter ...
Страница 68: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 68 ATEX for Sensor ...
Страница 70: ...Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08 2016 70 IEC Ex for Sensor ...
Страница 79: ...www norrscope com ...