Chapter 8 List of Data Settings
8 - 1
8.1 Precautions for Data Setting
The default display mode limits the screens (parameters) that can be displayed on the monitor. To enable the display of all parameters, specify "00" (full display) for the function code display
restriction (b037).
To enable the parameters to be changed while the inverter is operating, specify "10" for the software lock mode selection (b031).
8.2 Monitoring Mode
With the default settings, the monitor always displays the data output according to the output frequency monitoring (d001) after power-on. To change the initial display content, change the setting
of the initial-screen selection (b038) as required.
Code
Function name
Monitored data or setting
Default
Setting during
operation
(allowed or not)
Change during
operation
(allowed or not)
Page
d001
Output frequency monitoring
0.00 to 99.99, 100.0 to 400.0 (Hz)
−
{
−
4-1
d002
Output current monitoring
0.0 to 999.9, 1000 to 9999 (A)
−
−
−
4-1
d003
Rotation direction minitoring
F (forward rotation), o (stopped), r (reverse rotation)
−
−
−
4-1
d004
Process variable (PV), PID feedback
monitoring
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990),
⎡
100 to
⎡
999 (100000 to 999000)
−
−
−
4-1
d005
Intelligent input terminal status
(Example)
Terminals FW, 7, 2, and 1: ON
Terminals 8, 6, 5, 4, and 3: OFF
−
−
−
4-2
d006
Intelligent output terminal status
(Example)
Terminals 12 and 11: ON
Terminals AL, 15, 14, and 13: OFF
−
−
−
4-2
d007
Scaled output frequency monitoring
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
−
{
−
4-2
d008
Actual-frequency monitoring
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz)
−
−
−
4-3
d009
Torque command monitoring
-150. to +150. (%)
−
−
−
4-3
d010
Torque bias monitoring
-150. to +150. (%)
−
−
−
4-3
d012
Torque monitoring
-150. to +150. (%)
−
−
−
4-3
d013
Output voltage monitoring
0.0 to 600.0 (V)
−
−
−
4-3
d014
Power monitoring
0.0 to 999.9 (kW)
−
−
−
4-3
d015
Cumulative power monitoring
0.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990),
⎡
100 to
⎡
999 (100000 to 999000)
−
−
−
4-4
d016
Cumulative operation RUN time
monitoring
0. to 9999., 1000 to 9999 (10000 to 99990),
⎡
100 to
⎡
999 (100000 to 999000) (hr)
−
−
−
4-4
d017
Cumulative power-on time monitoring
0. to 9999., 1000 to 9999 (10000 to 99990),
⎡
100 to
⎡
999 (100000 to 999000) (hr)
−
−
−
4-4
d018
Heat sink temperature monitoring
-020. to 200.0 (
°
C)
−
−
−
4-4
d019
Motor temperature monitoring
-020. to 200.0 (
°
C)
−
−
−
4-4
d022
Life-check monitoring
1: Capacitor on main circuit board
2: Cooling-fan speed drop
−
−
−
4-5
d023
Program counter
0 to 1024
−
−
−
4-5
d024
Program number monitoring
0000 to 9999
−
−
−
4-5
FW
8 7
6
5
4
3 2 1
AL 15 14 13 12
11
2 1
ON
OFF
Содержание SJ700B SERIES
Страница 15: ...Contents xiii Index Index Index 1 ...
Страница 17: ......
Страница 22: ......
Страница 45: ......
Страница 59: ......
Страница 223: ......
Страница 237: ......
Страница 245: ......
Страница 250: ...Chapter 7 Specifications 7 5 SJ700B 185 to 300HFF SJ700B 370HFF 5 Cable hole φ25 3 Cable hole 42 x 42 5 ...
Страница 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Страница 253: ......