Chapter 4 Explanation of Functions
4 - 136
(v) Performing a loopback test [08h]
The loopback test function is used to check the communication between the external control system
(master) and the inverter (slave).
(Example)
When performing a loopback test with the inverter at slave address "1":
The diagnosis subcode only conforms to the echoing of query data (00h, 00h). It cannot be used for other
commands.
(vi) Writing data to multiple coils [0Fh]
This function rewrites data in sequential coils.
(Example)
When updating the status of the intelligent input terminals [1] to [6] of the inverter at slave address "5":
The status of the intelligent input terminals is updated to the status shown in the following table:
Intelligent
input
terminal
1 2 3 4 5 6
Coil
number
7 8 9 10 11 12
Terminal status
ON
ON
ON
OFF
ON
OFF
If the function to write data to multiple coils cannot be executed normally, the inverter will return an
exception response. For details, see Item (viii), "Exception response."
Query
Field name
Sample setting
(hexadecimal)
1 Slave address (*1)
01
2 Function
code
08
3 Diagnosis subcode (upper digit)
00
4 Diagnosis subcode (lower digit)
00
5 Data (upper digit)
Arbitrary
6 Data (lower digit)
Arbitrary
7 CRC-16 code (upper digit)
CRC
8 CRC-16 code (lower digit)
CRC
*1 This query cannot be broadcasted.
Response
Field name
Sample setting
(hexadecimal)
1
Slave address
01
2
Function code
08
3
Diagnosis subcode (upper digit)
00
4
Diagnosis subcode (lower digit)
00
5
Data (upper digit)
Arbitrary
6
Data (lower digit)
Arbitrary
7
CRC-16 code (upper digit)
CRC
8
CRC-16 code (lower digit)
CRC
Query
Field name
Sample setting
(hexadecimal)
1
Slave address (*1)
05
2 Function
code
0F
3
Starting coil number
(upper digit) (*2)
00
4
Starting coil number
(lower digit) (*2)
06
5
Number of coils (upper digit)
00
6
Number of coils (lower digit)
06
7
Number of data bytes (*3)
02
8
Updating data (upper digit) (*3)
17
9
Updating data (lower digit) (*3)
00
10 CRC-16 code (upper digit)
DB
11 CRC-16 code (lower digit)
3E
*1 If this query is broadcasted, no inverter will return any
response.
*2 Note that the starting coil number is 1 less than the
actual coil number of the coil to which the data is to be
written first.
*3 The updating data consists of the upper and lower digits.
Even when updating an odd number of data bytes, add
1 to the number of data bytes to make it an even
number before specifying the number of data bytes.
Response
Field name
Sample
setting
(hexadecimal)
1
Slave address
05
2
Function code
0F
3
Starting coil number (upper digit)
00
4
Starting coil number (lower digit)
06
5
Number of coils (upper digit)
00
6
Number of coils (lower digit)
06
7
CRC-16 code (upper digit)
34
8
CRC-16 code (lower digit)
4C
Содержание SJ700B SERIES
Страница 15: ...Contents xiii Index Index Index 1 ...
Страница 17: ......
Страница 22: ......
Страница 45: ......
Страница 59: ......
Страница 223: ......
Страница 237: ......
Страница 245: ......
Страница 250: ...Chapter 7 Specifications 7 5 SJ700B 185 to 300HFF SJ700B 370HFF 5 Cable hole φ25 3 Cable hole 42 x 42 5 ...
Страница 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Страница 253: ......