Chapter 8 List of Data Settings
8 - 5
Code
Function name
Monitored data or setting
Default
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
A081
AVR function select
00 (always on), 01 (always off), 02 (off during deceleration)
02
¯
¯
AV
R
A082
AVR voltage select
400 V class: 380, 400, 415, 440, 460, 480 (V)
230/400
¯
¯
4-11
A085
Operation mode selection
00 (normal operation), 01 (energy-saving operation), 02 (fuzzy operation) 00
¯
¯
A086
Energy saving mode tuning
0.1 to 100.0
50.0
{
{
4-32
A092
Acceleration (2) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00
{
{
A292
Acceleration (2) time setting, 2nd
motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00
{
{
A392
Acceleration (2) time setting, 3rd
motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00
{
{
A093
Deceleration (2) time setting
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00
{
{
A293
Deceleration (2) time setting, 2nd
motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00
{
{
A393
Deceleration (2) time setting, 3rd
motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
15.00
{
{
A094
Select method to switch to
Acc2/Dec2 profile
00 (switching by 2CH terminal), 01 (switching by setting), 02 (switching only when
rotation is reversed)
00
¯
¯
A294
Select method to switch to
Acc2/Dec2, 2nd motor
00 (switching by 2CH terminal), 01 (switching by setting), 02 (switching only when
rotation is reversed)
00
¯
¯
A095
Acc1 to Acc2 frequency transition
point
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
¯
A295
Acc1 to Acc2 frequency transition
point, 2nd motor
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
¯
A096
Dec1 to Dec2 frequency transition
point
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
¯
A296
Dec1 to Dec2 frequency transition
point, 2nd motor
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
¯
4-30
A097
Acceleration curve selection
00 (linear), 01 (S curve), 02 (U curve), 03 (inverted-U curve), 04 (EL-S curve)
00
¯
¯
O
per
a
tion
m
ode and
acc
e
ler
a
ti
on/
deceler
a
tion
fu
nct
ion
A098
Deceleration curve setting
00 (linear), 01 (S curve), 02 (U curve), 03 (inverted-U curve), 04 (EL-S curve)
00
¯
¯
4-31
A101
[OI]-[L] input active range start
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
A102
[OI]-[L] input active range end
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
A103
[OI]-[L] input active range start
current
0. to "[OI]-[L] input active range end current" (%)
20.
¯
{
A104
[OI]-[L] input active range end
current
"[OI]-[L] input active range start current" to 100. (%)
100.
¯
{
A105
[OI]-[L] input start frequency
enable
00 (external start frequency), 01 (0 Hz)
00
¯
{
A111
[O2]-[L] input active range start
frequency
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
A112
[O2]-[L] input active range end
frequency
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
A113
[O2]-[L] input active range start
voltage
-100. to 02 end-frequency rate (%)
-100.
¯
{
Ext
e
rnal f
requen
cy
adjus
tm
en
t
A114
[O2]-[L] input active range end
voltage
"02 start-frequency rate" to 100. (%)
100.
¯
{
4-14
A131
Acceleration curve constants
setting
01 (smallest swelling) to 10 (largest swelling)
02
¯
{
Acceler
ation
and
deceler
ation
A132
Deceleration curve constants
setting
01 (smallest swelling) to 10 (largest swelling)
02
¯
{
4-31
A141
Operation-target frequency
selection 1
00 (digital operator), 01 (keypad potentiometer), 02 (input via O), 03 (input via OI), 04
(external communication), 05 (option 1), 06 (option 2), 07 (pulse-string frequency input)
02
¯
{
A142
Operation-target frequency
selection 2
00 (digital operator), 01 (keypad potentiometer), 02 (input via O), 03 (input via OI), 04
(external communication), 05 (option 1), 06 (option 2), 07 (pulse-string frequency input)
03
¯
{
A143 Operator
selection
00 (addition: A141 + A142), 01 (subtraction: A141 - A142), 02 (multiplication: A141 x
A142)
00
¯
{
4-13
A145
Frequency to be added
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
O
per
a
tion-
tar
g
e
t
fr
equency
A146
Sign of the frequency to be added
00 (frequency c A145), 01 (frequency command - A145)
00
¯
{
4-14
A150
EL-S-curve acceleration
ratio 1
0. to 50. (%)
25.
¯
¯
A151
EL-S-curve acceleration
ratio 2
0. to 50. (%)
25.
¯
¯
A152
EL-S-curve deceleration
ratio 1
0. to 50. (%)
25.
¯
¯
Acceler
a
ti
on and
deceler
at
ion
A153
EL-S-curve deceleration
ratio 2
0. to 50. (%)
25.
¯
¯
4-31
*1 This setting is valid only when the OPE-SR is connected.
Содержание SJ700B SERIES
Страница 15: ...Contents xiii Index Index Index 1 ...
Страница 17: ......
Страница 22: ......
Страница 45: ......
Страница 59: ......
Страница 223: ......
Страница 237: ......
Страница 245: ......
Страница 250: ...Chapter 7 Specifications 7 5 SJ700B 185 to 300HFF SJ700B 370HFF 5 Cable hole φ25 3 Cable hole 42 x 42 5 ...
Страница 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Страница 253: ......