Chapter 8 List of Data Settings
8 - 11
Code
Function name
Monitored data or setting
Default
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
C038
Low-current indication signal output
mode selection
00 (output during acceleration/deceleration and constant-speed operation), 01
(output only during constant-speed operation)
01
¯
{
C039
Low-current indication signal
detection level
0.0 to 1.50 x "rated current" (A)
Rated
current of
inverter
{
{
4-69
C040
Overload signal output mode
00 (output during acceleration/deceleration and constant-speed operation), 01
(output only during constant-speed operation)
01
¯
{
C041
Overload level setting
0.0 to 1.50 x "rated current" (A)
Rated
current of
inverter
{
{
4-40
C042
Frequency arrival setting for accel.
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
C043
Frequency arrival setting for decel.
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
4-62
C044
PID deviation level setting
0.0 to 100.0 (%)
3.0
¯
{
4-29
C045
Frequency arrival setting for
acceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
C046
Frequency arrival setting for
deceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
4-62
C052
Maximum PID feedback data
0.0 to 100.0 (%)
100.0
¯
{
C053
Minimum PID feedback data
0.0 to 100.0 (%)
0.0
¯
{
4-29
C055
Over-torque (forward-driving) level
setting
0. to 150. (%)
100.
¯
{
C056
Over-torque (reverse regenerating)
level setting
0. to 150. (%)
100.
¯
{
C057
Over-torque (reverse driving) level
setting
0. to 150. (%)
100.
¯
{
C058
Over-torque (forward regenerating)
level setting
0. to 150. (%)
100.
¯
{
4-65
C061
Electronic thermal warning level
setting
0. to 100. (%)
80.
¯
{
4-38
C062
Alarm code output
00 (disabling), 01 (3 bits), 02 (4 bits)
00
¯
{
4-65
C063
Zero speed detection level
0.00 to 99.99, 100.0 (Hz)
0.00
¯
{
4-64
Levels and ou
tput t
e
rm
inal sta
tus
C064
Heat sink overheat warning level
0. to 200.0 (
°
C)
120.
¯
{
4-68
C071
Communication speed selection
02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06 (19,200
bps)
04
¯
{
C072
Node allocation
1. to 32.
1.
¯
{
C073
Communication data length selection
7 (7 bits), 8 (8 bits)
7
¯
{
C074
Communication parity selection
00 (no parity), 01 (even parity), 02 (odd parity)
00
¯
{
C075
Communication stop bit selection
1 (1 bit), 2 (2 bits)
1
¯
{
C076
Selection of the operation after
communication error
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring
errors), 03 (stopping the motor after free-running), 04 (decelerating and stopping
the motor)
02
¯
{
C077
Communication timeout limit before
tripping
0.00 to 99.99 (s)
0.00
¯
{
C078
Communication wait time
0. to 1000. (ms)
0.
¯
{
Com
m
unica
ti
on f
unc
ti
on
C079
Communication mode selection
00(ASCII), 01(Modbus-RTU)
00
¯
{
4-113
C081
[O] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
Factory
setting
{
{
C082
[OI] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
Factory
setting
{
{
C083
[O2] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
Factory
setting
{
{
−
C085
Thermistor input tuning
0.0 to 999.9, 1000.
Factory
setting
{
{
4-72
Adjust
m
ent
C091
Debug mode enable
(Do not change this parameter, which is intended for factory adjustment.)
00
¯
¯
−
C101
Up/Down memory mode selection
00 (not storing the frequency data), 01 (storing the frequency data)
00
¯
{
4-56
C102 Reset
mode
selection
00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off),
02
(enabling resetting only upon tripping [resetting when RS is on]),
03(resetting only
trip)
00
{
{
Oth
e
rs
C103
Restart mode after reset
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting with
active matching frequency)
00
¯
{
4-54
C105
FM gain adjustment
50. to 200. (%)
100.
{
{
4-73
C106
AM gain adjustment
50. to 200. (%)
100.
{
{
C107
AMI gain adjustment
50. to 200. (%)
100.
{
{
C109
AM bias adjustment
0. to 100. (%)
0.
{
{
Me
te
r
adjust
m
en
t
C110
AMI bias adjustment
0. to 100. (%)
20.
{
{
4-74
Содержание SJ700B SERIES
Страница 15: ...Contents xiii Index Index Index 1 ...
Страница 17: ......
Страница 22: ......
Страница 45: ......
Страница 59: ......
Страница 223: ......
Страница 237: ......
Страница 245: ......
Страница 250: ...Chapter 7 Specifications 7 5 SJ700B 185 to 300HFF SJ700B 370HFF 5 Cable hole φ25 3 Cable hole 42 x 42 5 ...
Страница 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Страница 253: ......