Chapter 4 Explanation of Functions
4 - 111
4.3.20 Servo-on function
The servo-on function allows you to set the inverter in a
speed-servo locking state with a signal input via an input terminal
during operation. This function is effective when "05" (vector control
with sensor) is specified as the V/F characteristic curve selection
(A044).
To use this function, assign function "54" (SON) to an intelligent input terminal.
After the SON function has been assigned, the inverter accepts an operation command only when the
SON terminal is on.
If the SON terminal is turned off while the inverter is operating the motor, the inverter sets the motor into
the free-running state. If the SON terminal is subsequently turned on, the inverter restarts the motor
according to the setting of the festart mode after FRS (b088).
This function cannot be used together with the forcing function (55: FOC). If both the FOC and SON
functions are assigned to different intelligent input terminals, the FOC function has priority over the SON
function (the SON function cannot be used).
A044: V/F characteristic curve selection,
1st motor
C001 to C008: Terminal [1] to [8] functions
Related code
Restarting according to
the setting of "b088"
The inverter does not
operate the motor because
the SON terminal is off.
SON
FW(RV)
Output frequency
Speed-servo locking state
Free-running
ON ON
ON ON
ON
Содержание SJ700B SERIES
Страница 15: ...Contents xiii Index Index Index 1 ...
Страница 17: ......
Страница 22: ......
Страница 45: ......
Страница 59: ......
Страница 223: ......
Страница 237: ......
Страница 245: ......
Страница 250: ...Chapter 7 Specifications 7 5 SJ700B 185 to 300HFF SJ700B 370HFF 5 Cable hole φ25 3 Cable hole 42 x 42 5 ...
Страница 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Страница 253: ......