Chapter 2 Installation and Wiring
2 - 4
Section to be cut off
Joint
2.1.2 Backing plate
(1) For models with 30 kW or less capacity
On the backing plate, cut the joints around each section to be cut off with cutting pliers or a cutter,
remove them, and then perform the wiring.
(2) For the models with 37 kW or more
1) For wiring without using conduits
Cut an X in each rubber bushing of the backing plate with cutting pliers or a cutter, and then perform
the wiring.
2) For wiring using conduits
Remove the rubber bushings from the holes to be used for wiring with conduits, and then fit conduits
into the holes.
Note: Do not remove the rubber bushing from holes that are not used for wiring with a conduit.
If a cable is connected through the plate hole without a rubber bushing and conduit, the cable
insulation may be damaged by the edge of the hole, resulting in a short circuit or ground fault.
Backing plate
Rubber bushing