Safety Instructions
vii
10.Distribution fuse / circuit breaker size marking is included in the manual to indicate that the unit shall be
connected with a Listed inverse time circuit breaker, rated 600 V with the current ratings as shown in the
table below:
11.“Field wiring connection must be made by a UL Listed and CN closed-loop terminal connector sized for
the wire gauge involved. Connector must be fixed using the crimp tool specified by the connector
manufacturer.”, or equivalent wording included in the manual.
Model No.
Fuse Size (A)
Circuit Breaker (A)
Type Rating
Type Rating
SJ700B-055H J
30 A
Inverse time
30 A
SJ700B-075H
J
40 A
Inverse time
40 A
SJ700B-110H
J
60 A
Inverse time
60 A
SJ700B-150H
J
100A
Inverse time
100 A
SJ700B-185H
J
100 A
Inverse time
100 A
SJ700B-220H
J
100 A
Inverse time
100 A
SJ700B-300H
J
125 A
Inverse time
125 A
SJ700B-370H
J
175 A
Inverse time
175 A
SJ700B-450H
J
225 A
Inverse time
225 A
SJ700B-550H
J
250 A
Inverse time
250 A