Chapter 2 Installation and Wiring
2 - 21
2.2.5 Selection and wiring of regenerative braking resistor (on 5.5 kW to 30 kW models)
The SJ700B series inverter models with capacities of 5.5 to 30 kW have an internal regenerative braking
circuit.
Connecting an optional regenerative braking resistor to RB and P terminals increases the regenerative
torque.
Without a resistor
connected
With a resistor
connected
Minimum connectable
resistor
Model
Motor capacity
(kW)
Regenerative
torque (%)
Resistanc
e of
connecte
d resistor
(
Ω
)
Regenera
tive
torque
(
%
)
Resistanc
e
(
Ω
)
BRD
usage
rate
(
%
)
Minimum
resistance during
continuous
operation
(
Ω
)
SJ700B-055HFF 5.5
20
70 100 70 10
200
SJ700B-075HFF 7.5
20
70 100 70 10
200
SJ700B-110HFF 11
20
70 50 35 10
150
SJ700B-150HFF 15
10
50 70 35 10
150
SJ700B-185HFF
18.5
10
35 80 24 10
100
SJ700B-220HFF 22
10
35 70 24 10
100
SJ700B-300HFF 30
10
35 50 20 10
100