Chapter 8 Communication Functions
8 - 38
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1469h Up/Down memory mode selection
C101
R/W
0 (not storing the frequency data), 1
(storing the frequency data)
-
146Ah Reset mode selection
C102
R/W
0 (resetting the trip when RS is on), 1
(resetting the trip when RS is off), 2
(enabling resetting only upon tripping
[resetting when RS is on])
-
146Bh Restart mode after reset
C103
R/W
0 (starting with 0 Hz), 1 (starting with
matching frequency)
-
146Ch
UP/DWN clear mode
C104 R/W
0 (0Hz)
/1 (when power supply is turned on)
-
146Dh FM gain adjustment
C105
R/W 50 to 200
1 [%]
146Eh to
1485h (Reserved) -
-
-
-
1486h Output [11] on-delay time
C130
R/W 0 to 1000
0.1 [s]
1487h Output [11] off-delay time
C131
R/W 0 to 1000
0.1 [s]
1488h to
148F (Reserved) -
-
-
-
1490h Output RY on-delay time
C140
R/W 0 to 1000
0.1 [s]
1491h Output RY off-delay time
C141
R/W 0 to 1000
0.1 [s]
1492h Logic output 1 operand A
C142
R/W Same as the settings of C021 to C026
(except those of LOG1,no)
-
1493h Logic output 1 operand B
C143
R/W Same as the settings of C021 to C026
(except those of LOG1,no)
-
1494h Logical output 1 operator
C144
R/W 0 (AND), 1 (OR), 2 (XOR)
-
1495h to
149Ah (Reserved) -
-
-
-
149Bh Button sensitivity selection
C151 R/W 0 to 250 / no(255)
-
149Ch Scroll sensitivity selection
C152 R/W 1 to 20
-
149Dh to
14A3h (Reserved) -
-
-
-
14A4h Input [1] response time
C160
R/W 0 to 200
14A5h Input [2] response time
C161
R/W 0 to 200
14A6h Input [3] response time
C162
R/W 0 to 200
14A7h Input [4] response time
C163
R/W 0 to 200
14A8h Input [5] response time
C164
R/W 0 to 200
14A9h to
14ACh (Reserved) -
-
-
14ADh Multistage speed determination
time
C169
R/W 0 to 200
14A4h to
1500h unused -
-
Inaccessible -
(6) Registers (group H)
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1501h (Reserved)
-
- -
1502h (Reserved)
-
- -
1503h Motor capacity, 1st motor
H003
R/W 0(0.1kW)-11 (5.5kW)
-
1504h Motor poles setting, 1st motor
H004
R/W
0 (2 poles), 1 (4 poles), 2 (6 poles),
3 (8 poles)
-
1505h (Reserved)
-
- -
-
1506h (Reserved)
-
- -
-
1507h
Motor stabilization constant, 1st
motor
H006
R/W 0 to 255
1
1508h to
2102h
unused -
-
Inaccessible -
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...