Chapter 8 Communication Functions
8 - 39
(7) Registers (2
nd
control settings F group)
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
2103h Acceleration time (1),
2nd motor
F202 (high)
R/W
0 to 360000
0.01 [s]
2104h F202
(low)
R/W
2105h Deceleration time (1),
2nd motor
F203 (high)
R/W
0 to 360000
0.01 [s]
2106h F203
(low)
R/W
2107h to
2200h
unused -
-
Inaccessible -
(8) Registers (2
nd
control settings A,B,C,H group)
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
2201h
Frequency source, 2nd motor
A201
R/W
0 (keypad potentiometer), 1 (control
circuit terminal block), 2 (digital
operator), 3 (Modbus),10 (operation
function result)
-
2202h
Frequency source, 2nd motor
A202
R/W
1 (control circuit terminal block), 2
(digital operator), 3 (Modbus)
-
2203h
Base frequency, 2nd motor
A203
R/W
300 to "maximum frequency, 2nd
motor"
0.1 [Hz]
2204h
Maximum frequency,
2nd motor
A204
R/W
300 to 4000
0.1 [Hz]
2205h to
2215h
(Reserved) -
-
Inaccessible
-
2216h (Reserved)
-
- Inaccessible
-
2217h
Multispeed frequency setting,
2nd motor
A220 R/W
0 or "start frequency" to "maximum
frequency, 2nd motor"
0.01 [Hz]
2218h to
223Ah
(Reserved) -
-
Inaccessible
-
223Bh
Torque boost method selection,
2nd motor
A241 R/W
0 (manual torque boost), 1 (automatic
torque boost)
-
223Ch
Manual torque boost value, 2nd
motor
A242
R/W
0 to 200
0.1 [%]
223Dh
Manual torque boost frequency,
2nd motor
A243
R/W
0 to 500
0.1 [%]
223Eh
V/F characteristic curve
selection, 2nd motor
A244
R/W
0 (VC), 1 (VP), 2 (free V/f)
-
223Fh
V/f gain, 2nd motor
A245
R/W
20 to 100
1 [%]
2240h
Voltage compensation gain
setting for automatic torque
boost, 2nd motor
A246
R/W
0 to 255
1
2241h
Slippage compensation gain
setting for automatic torque
boost, 2nd motor
A247
R/W
0 to 255
1
2242h to
224Eh
(Reserved) -
-
Inaccessible
-
224Fh (Reserved)
-
- Inaccessible
-
2250h
Frequency upper limit,
2nd motor
A261 R/W
00 or "2nd minimum frequency limit"
to "maximum frequency, 2nd motor"
0.01 [Hz]
2251h (Reserved)
-
- Inaccessible
-
2252h
Frequency lower limit,
2nd motor
A262 R/W
00 or "start frequency" to "maximum
frequency, 2nd motor limit"
0.01 [Hz]
2253h to
2268h
(Reserved) -
-
Inaccessible
-
2269h
AVR function select, 2nd motor
A281
R/W
0 (always on), 1 (always off), 2 (off
during deceleration)
-
226Ah
AVR voltage select, 2nd motor
A282
R/W
200 V class: 0 (200)/1 (215)/2 (220)/3
(230)/4 (240)
400V class: 5(380)/ 6(400)/ 7(415)/
8(440)/ 9(460)/ 10(480)
226Bh to
226Eh
(Reserved) -
-
Inaccessible
-
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...