Chapter 8 Communication Functions
8 - 26
(3) Registers (group A)
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1201h Frequency
source
A001
R/W
0 (keypad potentiometer), 1 (control
circuit terminal block), 2 (digital
operator), 3 (Modbus), 10 (operation
function result)
-
1202h Run command source (*)
A002
R/W
1 (control circuit terminal block), 2
(digital operator), 3 (Modbus)
-
1203h Base frequency
A003
R/W 300 to "maximum frequency"
0.1 [Hz]
1204h Maximum frequency
A004
R/W 300 to 4000
0.1 [Hz]
1205h to
120Ah
(Reserved) -
-
-
-
120Bh (Reserved)
-
- -
-
120Ch
[O/OI] input active range start
frequency
A011
R/W 0 to 40000
0.01 [Hz]
120Dh (Reserved)
-
- -
-
120Eh
[O/OI] input active range end
frequency
A012
R/W 0 to 40000
0.01 [Hz]
120Fh
[O/OI] input active range start
voltage/current
A013 R/W
0 to "[O/OI]-[L] input active range end
voltage/current"
1 [%]
1210h
[O/OI] input active range end
voltage/current
A014 R/W
"[O/OI]-[L] input active range start
voltage/current" to 100
1 [%]
1211h [O/OI] input start frequency select
A015
R/W 0 (external start frequency), 1 (0 Hz)
-
1212h Analog input filter.
A016
R/W
1 to 30 or 31 (500 ms filter ±0.1 Hz with
hysteresis)
1
1213h (Reserved)
-
- -
-
1214h (Reserved)
-
- -
-
1215h Multi speed operation selection
A019
R/W 0 (binary), 1 (bit)
-
1216h (Reserved)
-
- -
-
1217h Multi-speed freq. 0
A020
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1218h (Reserved)
-
- -
-
1219h Multi-speed freq. 1
A021
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
121Ah (Reserved)
-
- -
-
121Bh Multi-speed freq. 2
A022
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
121Ch (Reserved)
-
- -
-
121Dh Multi-speed freq. 3
A023
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
121Eh (Reserved)
-
- -
-
121Fh Multi-speed freq. 4
A024
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1220h (Reserved)
-
- -
-
1221h Multi-speed freq. 5
A025
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1222h (Reserved)
-
- -
-
1223h Multi-speed freq. 6
A026
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1224h (Reserved)
-
- -
-
1225h Multi-speed freq. 7
A027
R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
*)After changing the setting, keep the time 40ms or longer before actually give run command.
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...