Chapter 13 Option
13 - 52
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
23
PID PID
Disable
ON
Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(
=
)
OFF
Has no effect on PID loop operation, which operates
normally if PID Enable is active (
=
)
24
PIDC PID
Reset
ON
Resets the PID loop controller. The main
consequence is that the integrator sum is forced to
zero
OFF
No effect on PID controller
27
UP
Remote Control UP
Function (motorized
speed pot.)
ON
Accelerates (increases output frequency) motor
from current frequency
OFF
Output to motor operates normally
28
DWN
Remote Control
Down Function
(motorized speed
pot.)
ON
Decelerates (decreases output frequency) motor
from current frequency
OFF
Output to motor operates normally
29
UDC
Remote Control Data
Clearing
ON
Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
must be set=
to enable this function to
work
OFF
UP/DWN frequency memory is not changed
31
OPE Operator
Control
ON
Forces the source of the output frequency setting
and the source of the Run command
to be from the digital operator
OFF
Source of output frequency set by
and
source of Run command set by
is used
32
SF1
Multi-speed Select,
Bit operation Bit 1
ON
Bit encoded speed select, Bit 1, logical 1
OFF
Bit encoded speed select, Bit 1, logical 0
33
SF2
Multi-speed Select,
Bit operation Bit 2
ON
Bit encoded speed select, Bit 2, logical 1
OFF
Bit encoded speed select, Bit 2, logical 0
34
SF3
Multi-speed Select,
Bit operation Bit 3
ON
Bit encoded speed select, Bit 3, logical 1
OFF
Bit encoded speed select, Bit 3, logical 0
39
OLR
Overload Restriction
Source Changeover
ON
Perform overload restriction
OFF Normal
operation
50
ADD
ADD frequency
enable
ON
Adds the
(add frequency) value to the output
frequency
OFF
Does not add the
value to the output
frequency
51
F-TM
Force Terminal
Mode
ON
Force inverter to use input terminals for output
frequency and Run command sources
OFF
Source of output frequency set by
and
source of Run command set by
is used
53
KHC Clear
watt-hour
data
ON Clear
watt-hour
data
OFF No
action
65
AHD
Analog command
hold
ON
Analog command is held
OFF
Analog command is not held
83
HLD Retain
output
frequency
ON
Retain the current output frequency
OFF No
retention
84
ROK
Permission of Run
command
ON Run
command
permitted
OFF
Run command is not permitted
86
DISP Display
limitation
ON Only a parameter configured in
is shown
OFF
All the monitors can be shown
no
no
No function
ON
(input ignored)
OFF (input
ignored)
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...