![Hitachi NES1-002LB Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/hitachi/nes1-002lb/nes1-002lb_quick-reference-manual_142305057.webp)
Chapter 6 Operation
6 - 4
6.5 How To Operate the Inverter
(A) Names and functions of components
Standard panel
Name Description
1) POWER LED
- Turns on (red) during inverter is powered up
2) Run command
LED
- Turns on (green) during inverter operation. (This turns ON either Run command
is given, or the inverter is giving out power. Therefore it keeps turning on during
0 Hz driving, or keeps turning on during deceleration period even after the run
command is OFF.
3) ALARM LED
- Turns on (red) when the inverter is in trip status.
- See section 6.8 for details on clearing alarms.
4) Key valid lamp
- Turns on (green) when the RUN/STOP/RESET is ready. It turns off when there
is a RUN command. If the run command is being given from the
RUN/STOP/RESET key, the lamp is being on during deceleration period even
after the run command is OFF. While Run command is given such as FW(RV)
terminal,if "RUN/STOP/RESET key" was pressed, even Run command is OFF,
the "Key valid lamp" is OFF until inverter is Stopped.
5)RUN/STOP/RESET
key
- Makes inverter run, stop and reset. RUN/STOP/RESET key is set default and it
can be made invalid by the key sensitivity selection (C151) to “no”.
- It restores from the trip state if the inverter is in trip state.
- If the ModBus communication is selected, it can be temporary changed to a
external operator mode if the inverter is powered up with pressing the
RUN/STOP/RESET key and keep it pressing 5seconds,and take off from the
key.. Changeover switch must be changed later on. Note 1)
6) RS422/RS485 port
(RJ45)
- This is a port for external operator, Modbus connection, or ProDrioveNext
(RS485/operator changeover switch must be operated) before Power ON. In
case of Modbus communication, it is necessary to set the changeover switch
and parameter (C070). Display of NES1-OP will be according to the parameter
set of b150 continuiously, if the external operator is connected while the
dedicated operator (NES1-OP) is integrated. Note2)
Note 1) It is necessary to set changeover switch and the parameter C070 for releasing the Modbus
communication. If the parameter C070 is set to Modbus, external operator via the RJ45 jack
cannot be used.
Note 2) Connecting work on RJ45 jack must be done during the inverter power off.
1) POWER LED
3) ALARM LED
2) Run command LED
6) RS422/RS485 port
4) Key valid lamp
5) RUN/STOP/RESET key
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...