Chapter 7 Explanation of Functions
7 - 10
Item
Function
code
Data Description
AVR function select
A081/A281
00
The AVR function is always enabled.
01
The AVR function is always disabled.
02
The AVR function is disabled at deceleration.
(*1)
AVR voltage select
A082/A282
200/215/220/230/240
Selectable on 200 V class inverter models
380/400/415/440/460/480
Selectable on 400 V class inverter models
AVR filter time
constant
A083 0.000
~
1.000 (s)
See diagram below. (*2)
AVR deceleration
gain
A084 50.
~
200.(%)
See diagram below. (*2)
*1 Disabling the AVR function at motor deceleration increases the energy loss on the decelerated motor
and decreases the energy regenerated on the inverter, which results in a shorter deceleration time.
*2 Operate regardless of the A081/A281.
Output voltage
A082/A282
Time
Input voltage
Output voltage of A081 = 00 or 02.
Time
A083
=
0
Deceleration start
A084
Large
Small
Example) If set to A081 = 02
Output voltage
A082/A282
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...