(D) Write in Holding Register [06h]
This function writes data in a specified holding register. An example follows:
Write “50Hz” as the first Multi-speed 0 (A020) in an inverter having slave address “5.”
This example uses change data “500(1F4h)” to set “50Hz” as the data resolution of the register
“1019h” holding the first Multi-speed 0 (A020) is 0.1Hz
Query: Response:
No.
Field Name
Example
(Hex)
No.
Field Name
Example
(Hex)
1
Slave address *1
05
1
Slave address
05
2
Function code
06
2
Function code
06
3
Register start address
*2
(high order)
12
3
Register start address *2
(high order)
12
4
Register start address
*2
(low order)
16
4
Register start address *2
(low order)
16
5 Change
data
(high order)
01 5
Change
data
(high order)
01
6 Change
data
(low order)
F4 6
Change
data
(low order)
F4
7
CRC-16 (high order)
6C
7
CRC-16 (high order)
6C
8
CRC-16 (low order)
E5
8
CRC-16 (low order)
E5
Note 1:
No response is made for a broadcasting query.
Note 2:
The PDU Register Number are addressed starting at zero. Therefore register numbered
“1217h” are addressed as “1216h”. Register address value (transmitted on Modbus line)
is 1 less than the Register Number.
When writing in a selected holding register fails, see the exception response.
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...