Chapter 6 Operation
6 - 12
(2) Method to perform driving in RUN/STOP/RESET key and perform frequency setting in volume
resistor
This is the operation method using Run command is given by "RUN/STOP/RESET key" &
Frequency setting is given by analog input such as O-L voltage, Accel&Decel time is 10 seconds. (If
you don't need to change such as Accel&Decel time, optional Operator is not required.) Below
diagram is to set the external Freq. setting connecting H-O-L volume to supply O-L voltage.
■
Setup
Function Name
Code
Data
Note
Frequency source
A001
01
(
Control circuit terminals
)
Default
The initial value of Acceleration/ Deceleration time is 10sec.
Please change the following parameters as needed.
Function Name
Code
Setting Range
Note
Acceleration time
F002
0.00 to 3600 sec.
default
:
10 sec.
Deceleration time
F003
0.00 to 3600 sec.
default
:
10 sec.
* One of the following is required when changing parameters on NE-S1 series inverters.
a) Dedicated operator (NES1-OP)
b) Digital operator c) 5-line LCD operator
d) Modbus e) PC programming tool (ProDriveNext)
■
Control circuit terminals wiring (Sink logic)
P24
PLC
L
O/OI
H
Frequency setting
resistor
Note)
The above is a method to perform
analog input(O/OI) by voltage input. It
is necessary for SW6 on the board to
be set for voltage input(default).
→
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...