Chapter 13 Option
13 - 35
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Units
A157
(PID sleep
delay)
PID sleep function
action delay time
Sets the delay time
for the action, set
range 0.0 to 25.5
seconds.
0.0
←
←
s
A158
(PID sleep
Release)
PID sleep function
return threshhold
A156 to 400.0(Hz)
0.00
←
←
Hz
A161
(VR start FQ)
[VR] input active range
start frequency
The output
frequency
corresponding to the
analog input range
starting point,
range is 0.00 to
400.00 Hz
0.00
←
←
Hz
A162
(VR end FQ)
[VR] input active range
end frequency
The output
frequency
corresponding to the
current input range
ending point,
range is 0.00 to
400.00 Hz
0.00
←
←
Hz
A163
(VR start %)
[VR] input active range
start %
The starting point
(offset) for the
current input range,
range is 0 to 100%
0.
←
←
%
A164
(VR end %)
[VR] input active range
end %
The ending point
(offset) for the
current input range,
range is 0 to 100%
100.
←
←
%
A165
(VR start FQ
select)
[VR] input start
frequency select
Two options; select
codes:
00
Use offset
(A161 value)
01
Use 0Hz
01
←
←
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...