Chapter 7 Explanation of Functions
7 - 39
7.5.19 Energy-saver operation
[A085/A086]
The energy-saver operation function allows you to automatically minimize the inverter output power while
the inverter is driving the motor at constant speed. This function is suited to operating a fan, pump, or other
load that has a reduced-torque characteristic.
To use this function, specify "01" for the operation mode selection (A085).
Use the energy saving mode tuning function (A086) to adjust the response and accuracy of the
energy-saver operation.
The energy-saver operation function controls the inverter operation comparatively slowly. Therefore, if a
sudden change in the load occurs (e.g., impact load is applied), the motor may stall, and, consequently,
the inverter may trip because of overcurrent.
Item Function
code
Data
Description
Operation mode selection
A085
00
Normal operation
01
Energy-saving operation
Item Function
code
Data
Response
Accuracy
Energy saving mode tuning
A086
0
100
Slow
Quick
High
Low
7.5.20 Stabilization constant setting
The stabilization constant setting function allows you to adjust the inverter to stabilize the motor operation
when the motor operation is unstable.
If the motor operation is unstable, check the motor capacity setting (H003/H203) and motor pole setting
(H004/H204) to determine whether the settings match the motor specifications. If they do not match,
readjust the settings. If the primary resistance of the motor is less than the standard motor specification, try
to increase the setting of "H006/H206 " step by step. Try to reduce the setting of "H006/H206 " if the
inverter is driving a motor of which the capacity is higher than the inverter rating.
You can also use the following methods to stabilize the motor operation:
1) Reducing the carrier frequency (b083)
2) Reducing the V/f gain setting (A045)
Item Function
code
Data
Description
Stabilization constant
H006/H206
0. to 255.
Increase or reduce the setting to stabilize
the motor.
V/f gain setting
A045/A245
20. to 100. (%)
Reduce the setting to stabilize the motor.
Carrier frequency setting
b083
2.0 to 15.0 (kHz)
Reduce the setting to stabilize the motor.
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...