Chapter 8 Communication Functions
8 - 31
(4) Registers (group B)
Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1301h Restart mode on power failure /
under-voltage trip
b001 R/W
0 (tripping), 1 (starting with 0 Hz), 2
(starting with matching frequency), 3
(tripping after deceleration and stopping
with matching frequency)
-
1302h Allowable under-voltage power
failure time
b002
R/W 3 to 250
0.1 [s]
1303h Retry wait time before motor
restart
b003
R/W 3 to 1000
0.1 [s]
1304h
Instantaneous power
failure/under-voltage trip alarm
enable
b004 R/W
0 (disabling), 1 (enabling), 2 (disabling
during stopping and decelerating to
stop)
-
1305h Number of restarts on power
failure/under-voltage trip events
b005
R/W 0 (16 times), 1 (unlimited)
-
1306h (Reserved) -
-
-
-
1307h (Reserved) -
-
-
-
1308h Restart frequency threshold
b007
R/W 0 to 40000
0.01 [Hz]
1309h Restart mode on over voltage /
over current
b008 R/W
0 (tripping), 1 (starting with 0 Hz), 2
(starting with matching frequency), 3
(tripping after deceleration and stopping
with matching frequency)
-
130Ah (Reserved) -
-
-
-
130Bh Number of retry on over voltage /
over current
b010
R/W 1 to 3
1 [times]
130Ch Retry wait time on over voltage /
over current
b011
R/W 3 to 1000
0.1 [s]
130Dh Level of electronic thermal
b012
R/W 2000 to 10000
0.01 [%]
130Eh Electronic thermal characteristic
b013
R/W
0 (reduced-torque characteristic), 1
(constant-torque characteristic), 2 (free
setting)
-
130Fh (Reserved)
-
-
Inaccessible
-
1310h Free setting, electronic thermal
frequency (1)
b015
R/W 0 to 400
1 [Hz]
1311h Free setting, electronic thermal
current (1)
b016
R/W 0 to 10000
0.01 [%]
1312h Free setting, electronic thermal
frequency (2)
b017
R/W 0 to 400
1 [Hz]
1313h Free setting, electronic thermal
current (2)
b018
R/W 0 to 10000
0.01 [%]
1314h Free setting, electronic thermal
frequency (3)
b019
R/W 0 to 400
1 [Hz]
1315h Free setting, electronic thermal
current (3)
b020
R/W 0 to 10000
0.01 [%]
1316h Overload restriction operation
mode
b021 R/W
0 (disabling), 1 (enabling during
acceleration and constant-speed
operation), 2 (enabling during
constant-speed operation)
-
1317h Overload restriction level
b022
R/W 2000 to 20000
0.01 [%]
1318h Deceleration rate at overload
restriction
b023
R/W 1 to 30000
0.1 [
s
]
1319h Overload restriction operation
mode (2)
b024 R/W
0 (disabling), 1 (enabling during
acceleration and constant-speed
operation), 2 (enabling during
constant-speed operation)
-
131Ah Overload restriction level 2
b025
R/W 2000 to 20000
0.01 [%]
131Bh Deceleration rate at overload
restriction (2)
b026
R/W 1 to 30000
0.1 [
s
]
131Ch Over current suppression enable
b027
R/W 0 (disabling), 1 (enabling)
-
131Dh Current level of active freq.
matching
b028
R/W 1000 to 20000
0.01 [%]
131Eh Deceleration rate of active freq.
matching
b029
R/W 1 to 30000
0.1 [
s
]
Содержание NES1-002LB
Страница 9: ......
Страница 21: ......
Страница 25: ......
Страница 28: ...Chapter 3 Exterior Views 3 3 ...
Страница 29: ...Chapter 4 Installation This chapter describes how to install the inverter 4 1 Precautions for installation 4 1 ...
Страница 30: ......
Страница 35: ......
Страница 53: ......
Страница 75: ......
Страница 154: ......
Страница 196: ......
Страница 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Страница 204: ......
Страница 211: ......
Страница 219: ......
Страница 229: ......
Страница 289: ...Appendix Appendix A Appendix A 1 ...
Страница 290: ......
Страница 292: ...Appendix Appendix 2 ...